Unit type: CJ1 CPU Bus Unit.
Product Name: Controller Link Unit.
Specifications:Communications cable,
Wired shielded wisted-pair cable ;
Communications type,
Data links and message service;
Duplex support, No;
Max. Units mountable per CPU Unit, 8;
No. of unit numbers allocated: 1.
Current consumption : 5V, 0 CJ1W-CLK21-V1 PDF datasheet. 35A; 24V,--.
Standards: UC1, N, L, CE.
New Controller Link Units,
Now with 4,000 Send Words
CJ1W-CLK21-V1
The Controller Link is an FA,
network that can send and receive,
large amounts of data easily,
and at high speed.
The Controller Link supports data,
links that enable sharing,
data between PLCs and computers,
and a message service that enables,
sending and receiving data whenever required CJ1W-CLK21-V1 PDF datasheet.
Systems can be flexibly built by using Repeater,
Units to enable T-branches, long-distance wiring,
and converting part of the network to optical cable. Unit classification: CJ1 Special I/O Units.
Product name: Process Input Units,
(Isolated type Units with Universal Inputs).
Input points: 4 inputs.
Signal range selection:
Set separately for each input.
Signal range:Fully universal
inputs: Pt100, JPt100, Pt1000, K,
J, T, L, R, S, B, 4 to 20 mA, 0 to 20 mA,
1 to 5 V, 0 to 5 V, 0 to 10 V CJ1W-CLK21-V1 PDF datasheet.
Conversion speed (resolution): Conversion,
speed: 250 ms/4 inputs.
Accuracy at ambient temperature of 25°C:
Accuracy: Platinum resistance thermometer,
input: ±0.3% of PV or ±0.8°C, whichever,
is larger) ±1 digit max. Thermocouple input:
(±0.3% of PV or ±1.5°C, whichever is larger),
±1 digit max. *1 Voltage or current input:
±0.3% of F.S. ±1 digit max.
External connection: Removable terminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0 CJ1W-CLK21-V1 PDF catalog. 32A; 24V, --.
Standards: UC1, L, CE.
A Single Unit Handling All Types of Inputs,
such as Temperature Sensor Inputs and,
Analog Signal Inputs (e.g., 4 to 20 mA or 1 to 5V).
A Unit supports four inpuut channels,
each of which can be set to a
platinum resistance thermometer, thermocouple,
and DC signal (current, voltage) CJ1W-CLK21-V1 PDF catalog.
All inputs are isolated.