OMRON
Home >> Download >> OMRON >> Manual Download >> CP1E-N40SDT-D OPERATION MANUAL ()

CP1E-N40SDT-D OPERATION MANUAL ()

Brand: OMRON
Product model: CP1E-N40SDT-D
Name: PLC
Sort: OPERATION MANUAL
File language: English
File size: 3.20MB
UM: 31.2K words.
DM: 6K words.
EM: 6Kx3 banks(18K) words.
Instruction processing time (basic instructions): 0.1 µ.s min.
No. of I/O points: 880 points.
Max. no.of con-necting Expansion I/O Racks: 2 Racks.
Max. no. of connecting High-density I/O Units(i.e., Group-2): Unavailable.
Max. no. of con-necting Special I/O Units: 10 CP1E-N40SDT-D OPERATION MANUAL.
RS-232C: NO.Output method: Transistor sinking CP1E-N40SDT-D
Inputs: ---.
Outputs: 8.Model: C200H-ID217.
No. of points: 32 pts.
Specifications: 24 VDC.
Weight: 250g max.Unit classification: CJ1 Special I/O Units.
Product name: Process Input Units,
(Isolated type Units with Universal Inputs).
Input points: 4 inputs.
Signal range selection:
Set separately for each input CP1E-N40SDT-D OPERATION MANUAL.
Signal range:Universal
inputs: Pt100 (3-wire), JPt100 (3-wire),
Pt1000 (3-wire), Pt100 (4-wire), K, J,
T, E, L, U, N, R, S, B, WRe5-26, PL II,
4 to 20 mA, 0 to 20 mA, 1 to 5V, 0 to 1.25V,
0 to 5V, 0 to 10V, ±100 mV selectable range,
-1.25 to 1.25 V, -5 to 5 V, -10 to 10V,
±10V selectable range, potentiometer.
Conversion speed (resolution): Resolution
(conversion speed): 1/256,000 (conversion cycle:
60 ms/ 4 inputs) 1/64,000 (conversion cycle:
10 ms/4 inputs) 1/16,000 (conversion cycle:
5 ms/4 inputs) CP1E-N40SDT-D OPERATION MANUAL.
Accuracy at ambient temperature of 25°C:
Standard accuracy: ±0.05% of F.S.
External connection: Removable terminal block.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.30A; 24V, --.
Standards: UC1, CE.
A Single Unit Handling All Types of Inputs,
such as Temperature Sensor Inputs and,
Analog Signal Inputs (e.g., 4 to 20 mA or 1 to 5V).
A Unit supports four input channels,
each of which can be set to a
platinum resistance thermometer, thermocouple,
and DC signal (current, voltage).
All inputs are isolated. Unit type: CJ1 Special I/O Units.
Product name: Analog Output Unit.
I/O points: 4 inputs ; 2 outputs.
Signal range selection:
Set separately for each input and output.
Signal range, Resolution: 1 to 5 V,
0 to 5 V, 0 to 10 V, -10 to 10 V,
4 to 20 mA.
Resolution: 1/4,000 (Settable to 1/8,000).
Conversion period: 1 ms/point,
(Settable to 500 μs/point).
Accuracy at ambient temperature of 25°C:
Voltage: ±0.2% of F.S. Current: ±0.2% of F.S;
Voltage: ±0.3% of F.S. Current: ±0.3% of F.S.
External connection: Removable terminal block.
External power supply: 24 VDC +10% -15%, 140mA max CP1E-N40SDT-D Manual.
No. of unit numbers allocated: 1.
Current consumption: 5V, 0.58A; 24V, --.
Standards: UC1, N, L, CE.
Consistent Microsecond Throughput:
Models with Direct Conversion Join the Lineup.
Anaalog Input Units for converting analog input,
signals into binary data CP1E-N40SDT-D Manual.
Analog Output Units for converting binary ,
data into analog output signals.
Related products
OMRON
CP1E CPU Units
CP1E-N60SDT-D
OMRON CP1E CPU Units CP1E-N60SDT-D
Product name: NS1- type CPU Units with 60 I
OMRON
CP1E CPU Units
CP1E-N40S1DT-D
OMRON CP1E CPU Units CP1E-N40S1DT-D
Product name: NS1- type CPU Units with 40 I
OMRON
CP1E CPU Units
CP1E-N30SDT-D
OMRON CP1E CPU Units CP1E-N30SDT-D
Product name: NS1- type CPU Units with 30 I
OMRON
CP1E CPU Units
CP1E-N60S1DT-D
OMRON CP1E CPU Units CP1E-N60S1DT-D
Product name: NS1- type CPU Units with 60 I