Capacity: 240 W.
Input voltage: 100 to 240 VAC.
Output voltage: 24 V.
Maximum cutoff output current (per branch): 3.8 A.
Total output current: 10 A.
Number of output branches: 6 branch outputs.
Communications functions: None.
Parameter settings: Not changeable .
A New Type of Power Supply That S8VM-10024P Installation and Operating Manual.
Provides Safety and Maintainability.
240- and 480-W power supplies with and digital circuit,
protectors in a single package
S8VM-10024P
Each branch output tripping current value can be easily,
set at 0.1-A increments.
Startup and shutdown sequence control included.
Various monitor displays and alarms (output voltage,
output current, maintenance forecast monitor,
temperature).
Conforms to UL Class 2 S8VM-10024P Installation and Operating Manual.
Mounts to DIN Rail. Control power supply voltage: 200/220 VAC.
Input: DC or AC (selectable), Input voltage range, 10 to 300 V.
Overvoltage/Undervoltage Monitoring.
Relay for AC and DC Input.
Detect overvoltages or undervoltages (switch select,
able) from 4 mV to 300 V.
Detect undercurrent, reverse current, or overcurrent in,
DC circuits using shunt (SDV-FL).
Detect three-phase AC current for under and/or overcur,
rent using current converter S8VM-10024P Installation and Operating Manual.
Available in 7 supply voltage configurations.
Single-function model with ON-delay, OFF-delay, or star,
tup lock settings (SDV-FH@T).
Select either AC or DC voltage input.
Polarity can be specified (SDV-FL) to enable easy re,
verse current detection.
Selectable reset value range from 2% to 30% of operat,
ing value (SDV-F).
LED operation indicator.
UL/CSA approval (SDV-F@). Category: incidental cover with under voltage detection function.
Structure: bottom mounting type.
Capacity: 30W.
Output voltage: 24V.
Output current: 0.65A.
Alarm output: -.
Built in OMRON''s original new under voltage detection function of small size,
Also contribute to the miniaturization of the device.
Built in support for determining the abnormal causes of the new under voltage detection function.
(S8VM- - P - 24A - racy type)
Power failure detection function with built-in hint output voltage abnormity.
(type 300/600/1500W)
A total of 8 kinds of capacity of 29 models, a complete range of products.
Meet RoHS instructions including lead free.
Humanized design of anti - shedding screw for terminal stage.
(except for the 300/600/1500W output terminals)
Supporrt finger touch protection to prevent electric shock S8VM-10024P Manual.
DIN guide rail simple installation.
Safety standards: CSA, C22.2 No.14/No.60950-1 UL508/60950-1,
EN50178, EN60950-1.
(300/600/1500W type, safety standard is not applicable whenn the fan is replaced by the customer S8VM-10024P Manual. )
Meet F47-0200 SEMI standards. (200V input)
High harmonic current limit: EN61000-3-2. (except for type 15/30W)
"