Standard function model: detection of under voltage.
Appearance: ADR shell.
Open circuit: voltage, no voltage, DC circuit breaker.
Rated voltage: AC110V.
Rated frequency: 50/60Hz.
Voltage adjustment range: 60-65-70-75-80-85-90V (7 shunt).
Time hopping: timing; -0.2-0.4-0.6-0.8-1.0
-1.2-1.4-1.6-1.8-2.0s (11 shunt).
Control power supply: No, and input common; there, DC operation.
Rating consumption VA: No, 6VA (input side);
Have, 2VA (input side) 10W (control power supply side)
V-15-1C26
Control: 1C, 1A AC110V 7.5Acos output with =0.4
(max 250V 825VA AC);
24V 5A L/R=7ms DC (max 125V 50W when DC).
Display: start display (LED display),
Action display (trip) manual reset.
Automatic experiment: -.
Quality: about 2kg.
External: Mount Searl N1.5.
Static voltage relay.
K2VR-S/K2VA-S type, high action reliability disk with static type UVR/OVR.
Accurate work through high reliability semiconductor circuits.
Type K2VU-S1 is the output contact, but will be closed when the voltage is not enough,
Therefore, the locking time sequence circuit of the circuit breaker is not required.
Within the hidden from the start to the 2S timer, can easily adjust the time.
The control power of the relay is not needed, which avoids the trouble of wiring.
Size: 96 x 96mm.
Category: power AC100 ~ 240V with.
Shell color: black.
Control output 1: position ratio with relay output.
Control output 2: position ratio with relay output.
Control mode: position ratio control.
Auxiliary output points: 2 points.
Event entry point: 2.
Transfer output: transfer output (special terminal).
Remote SP:4 to 20mA input.
Communication: RS-232C.
General thermostat new high performance (high resolution, high speed, high precision input) type products.
Support simple operation, preventive maintenance.
A new type of liquid crystal, which can communicate with the front through the infrared port, is adopted,
Visual angle, contrast can be improved.
High resolution 5 bit display / can display 0.01 degrees C.
High speed sampling period 60ms.
All models complete a variety of (to the thermocouple /Pt/ analog input switching), 1 machines to support a variety of sensors.
Also supports remote SP.
Add PV/SV status display function, convenient to check the state of the thermostat (automatic / manual, RUN/STOP, alarm),
Interactive display PV/SV.
By supporting software (Ver.4.0 CX-Thermo) to carry out a simple function (AND/OR logic and delay),
Be able to execute flexible contact output.
Increase the control output ON/OFF number counting function, can predict the temperature controller internal relay fault.
Position ratio type.
V-15-1C26 Operation manual / Instructions / Catalog download link:
/searchDownload.html?Search=V-15-1C26&select=5