Name: Basic Unit(gradient temperature control)(See note 1.).
Power supply voltage: 24 VDC supplied from the End Unit.
No. of control points: 2.
Control outputs 1 and 2: Voltage output: 2 points (for SSR drive)(See note 2.).
Control outputs 3 and 4: Transistor output: 2 points(sourcing).
Auxiliary output: None.
Functions: Heater burnout alarm, 2 (See note 3.); Event inputs, None.
Communications functions: G3ZA connection port,
RS-485 From End Unit, Port A, RS-485
A165W-J2AR
Input type: Thermocouple, platinum resistance thermometer,
analog voltage, and analog current selectable for each channel.
Terminal: Screw-less clamp.
Gradient Temperature Control to Achieve.
Consistent Layer Temperature.
Perform gradient temperature control ranging from 2 to 32 channels.
Perform 2-channel gradient temperature control for up to 16,
groups, or 32-channel gradient temperature control for up to 2 groups.
Set gradient temperature control or 2-PID control for each group.
Reduce design work for ladder programming with programless,
connections to Programmable Controllers. (The same feature,
as Standard-control EJ1 Models.).
Connect directly to the G3ZA Multi-channel Power Controller,
using optimum cycle control for high-accuracy control with minimal noise. Name: Temperature Controller (See note 1.).
Power supply: 24 VDC.
No. of control points: 2.
Control output: Analog output (current output) (See note 2.).
Auxiliary output: Transistor output: 2 pts (sourcing).
Functions: Transfer output (linear voltage output)(See note 2.), Heating or heat/cool,
control is selectable (See note 4.)Event input: 1 point per Unit.
Communications functions: RS-485.
Input type (See note 5.): Thermocouple.
New DIN Track Mounting Temperature.
Controller.
Two channels of temperature control available despite width of,
only 22.5 mm.
The Temperature Controller itself can be replaced without,
changing terminal wiring.
Use in combination with a compact Setting Display Unit to,
reduce communications programming requirements.
Front-panel LED indicators for easy operation monitoring.
Power supply and communications wiring not required between,
Units when mounted side-by-side.
CompoWay/F communications protocol supported.
UL, CSA, and CE Marking compliance.
A165W-J2AR Operation manual / Instructions / Catalog download link:
/searchDownload.html?Search=A165W-J2AR&select=5