Input capacity: 16 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min.
(between each input terminal and the V terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the V terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC);
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms (Default setting: 1 ms)
D4SL-4JDG-D
Number of circuits per common: 16 inputs/common.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current con sumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 180 g max.
Expansion functions: Enabled.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expansion unit per one I/O terminal unit.)
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary switch and with tool software.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance. Ontology: terminal type, analog input type.
Category: control output 1 point type (power supply AC100 ~ 240V).
Shell color: black.
Control output: relay output and long life.
Control mode: standard or heating cooling.
Auxiliary output points: 2 points.
A power supply for the detection of /ES1B fault, SSR fault and heater over current for heater use.
Event input points: -.
Transfer output: -.
Communication: -.
48mm general thermostat has been upgraded & function / performance upgrade.
Indicates that the accuracy is increased and the preventive maintenance function is increased,
Further performance improvement.
E5CN-U (insert type) add analog input and current output type.
Add PV/SV status display function, convenient to check the state of the thermostat (automatic / manual, RUN/STOP, alarm),
Interactive display PV/SV.
Increase the number of control output ON/OFF counting function, can prevent the maintenance of temperature controller internal relay.