OMRON
Home >> Products >> OMRON >> Master slave station products >> DeviceNet >> DRT2-MD32B-1 Board Terminals with MIL Connector

DRT2-MD32B-1 Board Terminals with MIL Connector

OMRON DRT2-MD32B-1 Manual And Instructions
DRT2-MD32B-1 datasheetPDF datasheet
DRT2-MD32B-1 PROGRAMMING MANUAL
DRT2-MD32B-1 INSTRUCTION Manual

OMRON DRT2-MD32B-1 Product information and technical parameters:
Brand: OMRON
Name: Board Terminals with MIL Connector
Model: DRT2-MD32B-1
Specifications: I/O, PNP (input: - common, output: + common), 16 inputs/16 outputs.
I/O connections: MIL connector.
Rated internal circuit power supply voltage:
Supplied from communications connector.
Rated I/O power supply voltage: 24 VDC.
First Board-type Terminals for Smart Slaves!
Easily modified to handle an array of I/O interfaces,
and eliminates much on-site wiring.
User boards attach easily to the DRT2-@D32BV(-1) using screws.

Name: e-CON Connectors.
Specifications: Inputs/Outputs;
8 inputs /8 outputs; NPN;
With Short-circuit and,
Disconnected Line Detection.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system DRT2-MD32B-1.
A wide variety of CompoNet Slave Units,
contribute to system size reduction DRT2-MD32B-1
Seven-segment Display on the Gateway Unit,
helps to detect errors on site.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error. Input capacity: 16 points.
Internal I/O common: NPN DRT2-MD32B-1.
ON voltage: 15 VDC min.
(between each input terminal and the V terminal)
OFF voltage: 5 VDC max.
(between each input terminal and the V terminal)
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms, 1 ms,
2 ms, 4 ms, 8 ms, 16 ms, 32 ms. (Default setting: 1 ms)
Number of circuits per common: 8 points/common DRT2-MD32B-1.
Input indicators: LED display (yellow).
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Input device supply current: 100 mA/point.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max.
Expansion functions: No.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks.
It is unnecessary to share the common terminal,
among multipple contacts DRT2-MD32B-1.
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,

switch and with tool software DRT2-MD32B-1.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenance.


...More relevant models >>>>