16 points.
I/O connections: M3 screw terminals.
Supplied from Basic Unit.
I/O power supply voltage: 24 VDC.
Sharing of Terminals.
Easy wiring with no sharing of terminals.
Easy-to-understand wiring locations.
No relay terminal block terminals required.
Detachable cassette-type circuit sections.
Name: e-CON Connectors.
Specifications: Outputs; 16 outputs; PNP;
Without Short-circuit and,
Disconnected Line Detection.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system DRT2-OD16TA.
A wide variety of CompoNet Slave Units,
contribute to system size reduction
DRT2-OD16TA
Seven-segment Display on the Gateway Unit,
helps to detect errors on site.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error. Input capacity: 16 points.
Internal I/O common: PNP.
ON voltage: 15 VDC min DRT2-OD16TA. (between each in,
put terminal and the G terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the G terminal).
OFF current: 1.0 mA max.
Input current: 6.0 mA max./input (at 24-VDC),
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
Input filter value: Without filter, 0.5 ms,
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
(Default setting: 1ms)
Number of circuits per common: 16 points/common DRT2-OD16TA.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
(Operates at 50 mA/point min.)
Easy wiring using industry standard,
e-CON connectors.
Special wiring tool is not necessary.
Digital I/O terminal with industry,
standard e-CON connectors.
A common tterminal is provided for,
each connector DRT2-OD16TA.
The I/O terminal and the sensors can,
be connected directly.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary,
sswitch and with tool software DRT2-OD16TA.
When setting the nodes with rotary switch,
setting is easy and node identification,
becomes possible for maintenance.