OMRON
Home >> Download >> OMRON >> Manual Download >> GX-OC1601 INSTRUCTION MANUAL ()

GX-OC1601 INSTRUCTION MANUAL ()

Brand: OMRON
Product model: GX-OC1601
Name: Digital Temperature Controllers
Sort: INSTRUCTION MANUAL
File language: English
File size: 1.67MB
Input capacity: 16 points.
Rated current (ON current): 0.5 A/output,
4.0 A/common.
Internal I/O common: PNP.
Residual voltage: 1.2 V max.
(0.5 ADC, between each output,
terminal and the V terminal)
Leakage current: 0.1 mA max.
ON delay: 0.5 ms max.
OFF delay: 1.5 ms max.
Number of circuits per common:
8 points/common GX-OC1601 INSTRUCTION MANUAL.
Output indicators: LED display (yellow) GX-OC1601
Isolation method: Photocoupler isolation.
I/O power supply method: Supply by I/O power supply.
Output device supply current: 100 mA/point.
Unit power supply current consumption: 90 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
I/O power supply current consumption: 5 mA max.
(for 20.4 to 26.4-VDC power supply voltage)
Weight: 370 g max GX-OC1601 INSTRUCTION MANUAL.
Expansion functions: No.
Output handling for communications errors:
Select either hold or clear.
Short-circuit protection function: No.
A common terminal is provided for each contact.
It eliminate the needs for relay terminal blocks.
It is unnecessary to share the common terminal,
among multiple contacts.
Easy-to-find wiring locations.
Detachable screw terminal block facilitates the maintenance GX-OC1601 INSTRUCTION MANUAL.
Input response time can be switched for high-speed processing.
Selectable node address setting methods: setting with rotary,
switch and with tool software.
When setting the nodes with rotary switch, setting is easy and,
node identification becomes possible for maintenance. Applicable I/O Relay Terminal: G70V-SID16P-1.
Type: Input.
Internal I/O circuit common: PNP (+ common).
Rated voltage: 24 VDC.
I/O Relay Terminals with 16 Points and,
Push-In Plus terminal blocks to,
Downsize Control Panels and Save Labor.
I/O Relay Terminals with 16 points to mount G2RV Slim I/O Relays.
Push-In Plus terminal blocks are used to save wiring woork in,
comparison with traditional screw terminals GX-OC1601 Manual. (Wiring time is,
reduced by 60%* in comparison with traditional screw terminals.).
Work is reduced ever further with one-step cable connection to the PLC.
Diode provided for ccoil surge absorption GX-OC1601 Manual.
Operation indicators for immediate recognition of I/O signal status.
Accepts G3RV Slim I/O SSRs.
DIN Track or screw mounting.
Related products