Input capacity: 16 points.
Internal I/O common: NPN.
ON voltage: 15 VDC min. (between each in,
put terminal and the V terminal).
OFF voltage: 5 VDC max. (between each in,
put terminal and the V terminal).
OFF current: 1.0 mA max.
3.0 mA min./input (at 17-VDC).
ON delay: 0.1 ms max.
OFF delay: 0.2 ms max.
1 ms, 2 ms, 4 ms, 8 ms, 16 ms, 32 ms.
Number of circuits per common: 16 points/common.
Input indicators: LED display (yellow).
Isolation method: No isolation.
I/O power supply method: Supplied from unit power supply.
Input device supply current: 50 mA/point.
Unit power supply current consumption: 150 mA max.
e-CON Connector insertion durability: 50 times.
Weight: 140 g max.
Expansion functions: No.
Short-circuit protection function: Available.
e-CON connectors.
Special wiring tool is not necessary.
standard e-CON connectors.
each connector.
be connected directly.
high-speed processing.
switch and with tool software.
becomes possible for maintenance.
Name: Expansion Units.
Specifications: inputs ;
16 inputs; PNP;
One Expansion Unit can be,
mounted to one CRT1-ID16(-1),
CRT1-OD16(-1), CRT1-ROS16,
or CRT1-ROF16 Digital I/O Slave.
Standards: CE, UC, UC1, N.
"Easy" and "Flexible" system expansion,
with linked CC-Link and CompoNet.
Branching is easily made with CompoNet GX-ID1618.
Wiring material cost can be reduced.
Bit-level I/O distribution reduces,
wiring in the system
GX-ID1618
A wide variety of CompoNet Slave Units,
contribute to system size reduction.
Seven-segment Display on the Gateway Unit,
helps to detect errors on site.
The Participation Flags and Communications,
Error Flags can be checked at the Host,
Controller to detect the location and,
content of the error GX-ID1618. Input capacity: 16 points.
Mounted relays: NY-5W-K-IE (Fujitsu Component).
Rated load: Resistance load,
250 VAC 2 A/output, common 8 A,
30 VDC 2 A/output, common 8 A.
Rated ON current: 3 A/output.
Maximum contact voltage: 250 VAC, 125 VDC.
Maximum contact current: 3 A/output.
Maximum switching capacity: 750 VAAC, 90 WDC.
Minimum applicable load(reference value): 5 VDC 1mA GX-ID1618.
Mechanical service life: 20,000,000 operations min.
Electrical service life: 100,000 operations min.
Number of circuits per common: 8 points/common.
Output indicators: LED display (yellow).
Isolation method: Relay isolation.
I/O power supply method: The relay drive power,
is supplied from the unit power supply.
Unit power supply current consumption:
210 mA max. (for 20.4 to 26.4-VDC power supply voltage).
Weight: 290 g max.
Expansion functions: Enabled.
Output handling for communica tions errors:
Select either hold or clear.
Short-circuit protection function: No.
High-speed digital I/O terminal with the,
screw type terminal block for EtherCAT,
communications.
Detachable screw terminal block facilitates,
the maintenance.
The expansion unit can be connected.
(One expanssion unit per one I/O terminal unit GX-ID1618. )
Input/output point can be flexibly increased,
depending on the system.
Input response time can be switched for,
high-speed processing.
Selectable node address setting methods:
setting with rotary sswitch and with tool software GX-ID1618.
When setting the nodes with rotary switch,
setting is easy and node identification becomes,
possible for maintenance.